NUTSCAN_SCAN_SNMP(3)						    NUT Manual						      NUTSCAN_SCAN_SNMP(3)

NAME
nutscan_scan_snmp - Scan network for SNMP devices. SYNOPSIS
#include <nut-scan.h> nutscan_device_t * nutscan_scan_snmp(const char * start_ip,const char * stop_ip,long timeout, nutscan_snmp_t * sec); DESCRIPTION
The nutscan_scan_snmp() function try to detect NUT compatible SNMP devices. It tries SNMP queries on every IP ranging from start_ip to stop_ip. Those IP may be either IPv4 or IPv6 addresses or host names. You MUST call nutscan_init(3) before using this function. This function waits up to timeout microseconds before considering an IP address does not respond to SNMP queries. A valid nutscan_snmp_t structure must be passed to this function. The nutscan_snmp_t structure contains the following members which must be filled as described below: char * 'community'; char * 'secLevel'; char * 'secName'; char * 'authPassword'; char * 'privPassword'; char * 'authProtocol'; char * 'privProtocol'; If community is not NULL, SNMP v1 request are sent using this community. If community is NULL and secLevel is NULL, SNMP v1 is selected and community is set to "public". In the other cases, SNMP v3 is used. secLevel may be one of SNMP_SEC_LEVEL_NOAUTH, SNMP_SEC_LEVEL_AUTHNOPRIV or SNMP_SEC_LEVEL_AUTHPRIV. secName is the security name and must be non NULL. If secLevel is set to SNMP_SEC_LEVEL_AUTHNOPRIV, authPassword must be non NULL. If secLevel is set to SNMP_SEC_LEVEL_AUTHPRIV, authPassword and privPassword must be non NULL. If authProtocol is NULL, MD5 protocol is used. Else you can set authProtocol to either "MD5" or "SHA". If privProtocol is NULL, DES protocol is used. Else you can set privProtocol to either "AES" or "DES". peername and handle are used internally and do not need any initialization. RETURN VALUE
The nutscan_scan_snmp() function returns a pointer to a nutscan_device_t structure containing all found devices or NULL if an error occurs or no device is found. SEE ALSO
nutscan_init(3), nutscan_scan_usb(3), nutscan_scan_xml_http(3), nutscan_scan_nut(3), nutscan_scan_avahi(3), nutscan_scan_ipmi(3), nutscan_display_ups_conf(3), nutscan_display_parsable(3), nutscan_new_device(3), nutscan_free_device(3), nutscan_add_option_to_device(3), nutscan_add_device_to_device(3), nutscan_cidr_to_ip(3) Network UPS Tools 05/22/2012 NUTSCAN_SCAN_SNMP(3)

Check Out this Related Man Page

SNMP-UPS(8)							    NUT Manual							       SNMP-UPS(8)

NAME
snmp-ups - Multi-MIB Driver for SNMP UPS equipment NOTE
This man page only documents the hardware-specific features of the snmp-ups driver. For information about the core driver, see nutupsdrv(8). SUPPORTED HARDWARE
The snmp-ups driver automatically detects and supports a wide range of devices by loading various MIBS: ietf:: UPS that is RFC 1628 (UPS MIB) compliant, e.g. MGE UPS SYSTEMS, Liebert, perhaps others (default) mge MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP cards (ref 66062, 66045, 66074 and 66244) apcc APC AP9605, AP9606, AP9617, and AP9618 APC network management cards, as well as any others supporting the APC POWERNET MIB netvision Socomec Sicon UPS with Netvision Web/SNMP management card/external box pw Powerware devices with ConnectUPS SNMP cards aphel_genesisII Eaton Powerware ePDU Monitored aphel_revelation Eaton Powerware ePDU Managed raritan Various Raritan PDUs baytech Various BayTech PDUs cpqpower HP/Compaq AF401A management card, perhaps others cyberpower Cyberpower RMCARD201. Should also support RMCARD100 (net version), RMCARD202 and RMCARD301 EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5): mibs=name Set MIB compliance (default=auto, allowed entries: refer to the above SUPPORTED HARDWARE). With "auto", the driver will try a select set of SNMP objects until it finds one that the device responds to. community=name Set community name (default = public). Note that you require a RW community name to change UPS settings (as for a powerdown). snmp_version=version Set SNMP version (default = v1, the other allowed value is v2c) pollfreq=value Set polling frequency in seconds, to reduce network flow (default=30) notransferoids Disable the monitoring of the low and high voltage transfer OIDs in the hardware. This will remove input.transfer.low and input.transfer.high from the list of variables. This should only be used on APCC Symmetra equipment which has strangeness in the three-phase power reporting. secLevel=value Set the securityLevel used for SNMPv3 messages (default=noAuthNoPriv, allowed: authNoPriv,authPriv) secName=value Set the securityName used for authenticated SNMPv3 messages (no default) authPassword=value Set the authentication pass phrase used for authenticated SNMPv3 messages (no default) privPassword=value Set the privacy pass phrase used for encrypted SNMPv3 messages (no default) authProtocol=value Set the authentication protocol (MD5 or SHA) used for authenticated SNMPv3 messages (default=MD5) privProtocol=value Set the privacy protocol (DES or AES) used for encrypted SNMPv3 messages (default=DES) REQUIREMENTS
You will need to install the Net-SNMP package from http://www.net-snmp.org/ before building this driver. SNMP v3 also requires OpenSSL support from http://www.openssl.org. LIMITATION
Shutdown This driver does not provide a proper upsdrv_shutdown() function. There probably never will be one, since at the time this script should run (near the end of the system halt script), there will be no network capabilities anymore. Probably the only way to shutdown an SNMP UPS is by sending it a shutdown with delay command through upscmd(8) and hope for the best that the system will have finished shutting down before the power is cut. INSTALLATION
This driver is only built if the Net-SNMP development files are present on the system. You can also force it to be built by using "configure --with-snmp=yes" before calling make. IMPLEMENTATION
The hostname of the UPS is specified with the "port" value in ups.conf, i.e.: [snmpv1] driver = snmp-ups port = snmp-ups.example.com community = public snmp_version = v1 mibs = ietf pollfreq = 15 desc = "Example SNMP v1 device" [snmpv3] driver = snmp-ups port = 166.99.224.132 mibs = mge secLevel = authPriv secName = mysecurityname authPassword = myauthenticationpassphrase privPassword = myprivatepassphrase desc = "Example SNMP v3 device, with the highest security level" AUTHORS
Arnaud Quette, Dmitry Frolov Sponsored by Eaton http://www.eaton.com and originally by MGE UPS SYSTEMS http://www.mgeups.com/ SEE ALSO
The core driver: nutupsdrv(8) NUT SNMP Protocols Library Available at: http://www.networkupstools.org/protocols/snmp/ Internet resources: The NUT (Network UPS Tools) home page: http://www.networkupstools.org/ Network UPS Tools 05/21/2012 SNMP-UPS(8)